Qualité G652D G657A1 G657A2 OPGW Ground Wire Unitube Fiber Optic Cable Usine
Qualité G652D G657A1 G657A2 OPGW Ground Wire Unitube Fiber Optic Cable Usine

G652D G657A1 G657A2 OPGW Ground Wire Unitube Fiber Optic Cable

G652D G657A1 G657A2 OPGW Ground Wire Unitube Fiber Optic Cable
Propriétés de base
Pays D'Origine
Dong Guan en Chine
Nom De La Marque
MingTong
Certificat
ISO
Modèle De Produit
OPGW
Propriétés commerciales
MOQ
20km
Prix Unitaire
500-5000RNB/KM
Mode De Paiement
LC, T/T
Capacité D'Approvisionnement
200km/Day
Résumé du produit

Product Description Optical Fibre Composite Overhead Ground Wire (Uni-tube) Characteristics The protection and support of the optical fibers are provided by stainless steel tubes that are filled with hydrophobic gel. The tensile performance is good. The tubes have a small diameter and light weight, ...

Détails de produit
Mettre en évidence:

G652D OPGW Ground Wire

,

G657A2 OPGW Ground Wire

,

OPGW Unitube Fiber Optic Cable

Application: Replacemnet de fil de masse aérien
Fiber: G652D, G657A1, G657A2
Type: le professionnel fabrique
Cable Diameter: 9-18.2mm
Package: bobine fer-en bois
Highlight: G657A2 Fil de terre OPGW, G652D OPGW Fil de terre, G657A1 OPGW Fil de terre
Name: câble d'opgw
Description de produit
Product Description

Optical Fibre Composite Overhead Ground Wire (Uni-tube)


CharacteristicsG652D G657A1 G657A2 OPGW Ground Wire Unitube Fiber Optic Cable 0

The protection and support of the optical fibers are provided by stainless steel tubes that are filled with hydrophobic gel. The tensile performance is good. The tubes have a small diameter and light weight, which results in low additional load on the tower. The optical unit has an appropriate excess length of fiber, which makes it easy to assemble.


Attenuation

Bandwidth

Polarization Mode Dispersion


@850nm


@1300nm


@1310nm


@1550nm


@850nm


@1300nm

Individual Fibre

Design Link Value (M=20, Q=0.01%)

G652D ≤0.35dB/km ≤0.21dB/km ≤0.20ps/ km ≤0.1ps/ km
G655 ≤0.22dB/km ≤0.20ps/ km ≤0.1ps/ km
50/125μm ≤3.0dB/km ≤1.0dB/km ≥600MHz.km ≥1200MHz.km
62.5/125μm ≤3.5dB/km ≤1.0dB/km ≥200MHz.km ≥600MHz.km


Constructions and Performance


Classification Material Value




Construction

Optical Fibre G652D/G655 etc. 2 - 48
Protection Tube Stainless steel tube 1.5 - 6mm
Stranded Line AS wire/AA wire/Al Rod 1.5 - 6mm
Max. Diameter 18mm
Max. Cross Section 200mm2





Characteristic

According to the standards as DL/T 832, IEC60794-4-10, IEEE1138
Max. Tensile Strength (RTS ) (kN) 280
Max. Crush Strength(N/100mm) 2200
Max. Short Current Capacity (40℃-200℃)(kA2s) 100
Min. Bending Radius (Dynamic) 20D
Min. Bending Radius (Static) 15D
Environment Performance Installation (℃) -10 to +50
Transportation and Operation (℃) -40 to +65

Note: D is cable diameter.


Specific Type and Technical Data

No.

Technical Data

Product Type

Structure Type

Max. Fibre Count

Section of AS Wire
(mm2)

Diameter

(mm)

Cable Weight
(kg/km)

Rate Tensile Strength

(kN)

20℃DC

Resistance

(Ω/km)

Short Time Current Capacity

(40-200℃ kA2.s)

1 OPGW-24B1.3-40-[51;9] 6/3.0/20AS, Optical Unit 1/3.0 24 ≈40 9.0 ≤304 ≥51 ≤2.10 ≥9
2 OPGW-24B1.3-50-[58;11.5] 6/3.2/20AS, Optical Unit 1/3.2 24 ≈50 9.6 ≤345 ≥58 ≤1.82 ≥11.5
3 OPGW-48B1.3-70-[77;24] 6/3.8/20AS, Optical Unit 1/3.8 48 ≈70 11.4 ≤475 ≥77 ≤1.30 ≥24
4 OPGW-48B1.3-70-[42;38] 6/3.8/40AS, Optical Unit 1/3.8 48 ≈70 11.4 ≤340 ≥42 ≤0.70 ≥38

Other optical fibre type and count, stranded wire are available on request.

Mechanical and Environmental Testing Characteristics

Item

Test Method

Requirements




Tension

IEC 60794-1-2-E1

Load: according to cable structure

Sample length: no less than 10m, linked length no less than100m

Duration time: 1min


40%RTS no additional fibre strain(0.01%), no additional attenuation (0.03dB).

60%RTS fibre strain≤0.25%,additional attenuation≤0.05dB

(No additional attenuation after test).



Crush

IEC 60794-1-2-E3

Load: according to above table, three points Duration time: 10min


Additional attenuation at 1550nm ≤0.05dB/fibre; No damage to the elements



Water Penetration

IEC 60794-1-2-F5B

Time : 1 hour Sample length: 0.5m Water height: 1m



No water leakage.




Temperature Cycling

IEC 60794-1-2-F1

Sample length: No less than 500m Temperature range: -40℃ to +65℃

Cycles: 2

Temperature cycling test dwell time: 12h

The change in attenuation coefficient shall be less than 0.1dB/km at 1550nm.