aaac/acsr/aac conductor 50mm2 100mm2 acsr 1/0 conductor cable Application Features ABC systems are used for transmitting electricity in city power grids. They operate at voltages of up to 600/1000 volts and are primarily used for overhead single-phase and three-phase distribution of electricity, as ...

製品詳細
ハイライト:

Customized Aac Conductor

,

100mm2 Conductor Cable

Product Name: aaac/acsr/aacのコンダクター
Optical Union: ステンレス鋼の光学単位
Structure: 座礁する2つの層
Outer Sheath: アルミニウムで覆われた鋼線とアルミニウム合金
Package: 鉄木の巻き枠
Orientation Of Outer Strands: 左/右
Operating Temperature: -40°Cから+70°C
Highlight: アルミニウムクラッドスチールワイヤが縛られ、OPGWケーブル
Name: opgwケーブル
製品の説明

aaac/acsr/aac conductor 50mm2 100mm2 acsr 1/0 conductor cable

Application Features

ABC systems are used for transmitting electricity in city power grids. They operate at voltages of up to 600/1000 volts and are primarily used for overhead single-phase and three-phase distribution of electricity, as well as other purposes. They can operate within a stable temperature range of -10°C to 80°C, and they are economical because of their good electrical properties and lower cost compared to copper cables. They are flexible, making them easy to install and use in various applications. ABC systems are safe to use as they prevent electric short circuits and potential fire risks. They are durable and can withstand exposure to UV radiation and moisture, and are also corrosion-resistant. Additionally, ABC systems have an aesthetically pleasing finish and can adapt to the physical properties and electrical requirements of the African market and environment.

 

 

Specifications

 

Conductor Technical Structure
Unit
Value



Structure
Center: steel wire



Nos./mm
1/2.0
Layer 1:steel wire
6/2.0
Layer 2: Aluminum wire
10/2.57
Layer 3: Aluminum wire
16/2.57
Standard
/
GB/T1179/IEC 61089/ASTM B232 / B232M-2009 / B498
Stranding direction of outer layer
Direction
Right-hand
Conductor diameter
mm
16.28±1%
Cross section
mm2
156.8±1%
Conductor weight
kg/km
547.8±1%
Rated tensile strength
kN
52
Modulus of Elasticity
GPa
73.9
Coefficient of linear expansion
10-6/℃
18.9
Max. DC Resistance at 20℃
Ohm/ft
0.637

Lay ratio
Aluminum layer

times
16-wire layer 10-14
10-wire layer 10-16
Steel layer
6-wire layer 18-30
Properties of Aluminum Wire (Before Stranding)
Unit
Value
Diameter and tolerance
mm
2.57±0.03
Min. tensile strength
MPa
175
Min. elongation at 250mm
%
1.7
Max. resistivity at 20℃
Ω·mm2/m
0.02817
Properties of Steel wire (Before stranding)
Unit
Value
Diameter and tolerance
mm
2.0±0.02
Min. tensile strength
MPa
1410
Min. tension at 1% elongation
MPa
1280
Min elongation at 250 mm
%
3.5
Class of zinc coating
/
Class A
Zinc coating quality
g /mm²
230
Conductor diameter
MM
6.0
Rated tensile strength
KN
/

 

Packing & Shipping

 